Brand: FUJITSU
Reference: 3NGF89135
1x1 Fujitsu ACY71K-KA split duct Inverter medium pressure air conditioner
1x1 Fujitsu ACY71K-KA Air Conditioner
Cooling capacity kcal / h W 5850 (781-6354) 6800 (900-7400)
Heat output kcal / h W 6455 (781-7388) 7500 (900-8600)
Energy saving ratio (SEER / SCOP) 5.90 / 3.90
Energy saving ratio (EER / COP) 3.11 / 3.75
Cooling / heating energy class A + / A
Voltage / Phases / Frequency V / nº / Hz "230/1/50
Refrigeration / heating electricity consumption kW 2,0 / 2,19
Maximum cooling / heating start current A 12.6 / 12.6
Cooling / heating absorbed intensity A 9.7 / 8.8
Power supply (EU) 3x2.5 + N + T
3x2.5 + T electrical interconnection
Air flow unit Int. Min / Max m³ / h 580/1100
Air flow Unit Ext. (Max.) M³ / h 2885
Sound pressure Unit Int. A / M / B / Q / SQ dB (A) 31/29/27/25 / -
Sound pressure max. Unit Cooling / heating ext. DB (A) 55/54
Standard Static Pressure / Range Pa 35/30 - 150
Dimensions Int. Unit Height / Width / Depth mm 270/1135/700
Dimensions Unit Ext. Height / Width / Depth mm 632/799/290
Net weight Int. Unit / Ext. Unit Kg 35/38
Refrigeration connections diameter - Liquid / Gas Pul 1/4 "/ 1/2"
Max distances Total / Vertical m 25/20
R32 refrigerant
Refrigerant charge Kg (CO2eq-T) "" 1.25 (0.742)
Max distances precharged gas m 15
Additional load gr / m 20
Refrigeration / heating operating range ºC "-10 / 46 / -15 / 24
Hacéis presentaciones?
Buenas tardes, entendemos que pregunta si hacemos instalaciones.
No disponemos que personal para hacer instalaciones.
Buenas tardes. El equipo,es monofasico?. Sirve para calor y frio?. Un saludo y gracias
Buenas tardes Jesus, correcto el equipo es monofasico y lo podrás utilizar tanto para la producción de frío como calor. Atentamente, el equipo de Voltiks.