Brand: SCHNEIDER ELECTRIC
Reference: A9R84440
They automatically interrupt a circuit in the event of an insulation fault between active conductors and earth, equal to or greater than 10, 30 or 300 mA. ID differential switches are used in the domestic, tertiary and industrial.
Main
Acti 9 range
Product name Acti 9 iID40
Product or component type Residual current circuit breaker (RCCB)
Device short name IID
Number of poles 4P
Neutral position Left
[In] Rated current 40 A
Type AC mains voltage
Earth leakage sensitivity 300 mA
Protection delay against
earth leakage
Instantaneous
Class of protection against
earth leakage
Type AC
Complementary
Location of the device in the
system
Output
Mains frequency 50/60 Hz
[Ue] Rated operating voltage 380...415 V AC 50/ 60 Hz
Tripping technology
residual current
Independent of voltage
Connection and breaking capacity Idm 1500 A
Im 1500 A
Conditional current of
short circuit
10 kA
[Ui] Rated voltage of
insulation
500 V AC 50/60 Hz
[Uimp] Withstands
voltage peaks
6 kV
Surge current 250 A
Position indicator of the
contact
Yes
Type of control Lever
Disclaimer: This documentation is not intended to replace and should not be used to determine the suitability or reliability of these products for users' specific applications
14-Mar-2022 1
Mounting type Adjustable clip
Mounting bracket DIN rail
9 mm 8 steps
Height 91 mm
< p>Width 72 mmDepth 73.5 mm
Product weight 0.37 kg
Color White
Mechanical durability 20000 cycles
Electrical durability AC-1, state 1 15000 cycles
Description of the options of
locking
Locking device with padlock
Connections - terminals Single terminal top or bottom1…35 mm² rigid
Single terminal top or bottom1…25 mm² flexible
Single terminal top or bottom1…25 mm² flexible with terminal
Length of stripped cable to
connect terminals
1 4 mm for top or bottom connection
Tightening torque 3.5 Nm top or bottom
Environment
Standards EN/IEC 61008-1
IP degree of protection IP20 conforming to Enable / disable Ig
IP40 - cable type: modular enclosure) conforming to Enable / disable Ig
Pollution degree 3
Electromagnetic compatibility
Impulse withstand 8/20 µs, 250 A conforming to EN/IEC 61008-1
Ambient temperature from
operation
-5…60 °C
Ambient temperature for
storage
-40…85 °C
Packaging units
Type of package unit 1 PCE
Number of units in
packaging
1
Package weight (Lbs) 368 g
Package 1 Height 7.5 cm
Package 1 width 8.2 cm
Package 1 Length 10 cm
Type of unit of package 2 S03
Number of units in the
package 2
27< /p>
Weight of package 2 10,423 kg
Package 2 Height 30 cm
Width of package 2 30 cm
Length of package te 2 40 cm
Type of unit of package 3 P12
Number of units in the
package 3
216
2
14-mar-2022
Package 3 Weight 95.38 kg
Package 3 Height 80 cm
Width of package 3 80 cm
Package 3 Length 120 cm
Sustainability of the offer
Sustainable offer status Green Premium product
EU RoHS Directive Compliant
EU RoHS Declaration
Mercury Free Yes
Information on exemptions
from RoHS
Yes
China RoHS Regulation China RoHS Declaration
Product not in scope of China RoHS. Informative declaration of substances
Environmental communication Environmental profile of the product
WEEE In the European Union market, the product must be disposed of in accordance with a system of
specific waste collection and never end up in a garbage container.
Presence of halogens Product with halogen-free plastic content